Steril-Aire / UV Resources SLNX (SLN[X]) NEMA 4 UV-C Fixture
Explore SLN[X] coil and airstream applications, fixture differences, installation considerations and replacement-lamp identification with Tillman.

Start with your project requirements
Use our product selection tools to prepare the equipment details for review.
Explore UV-C products and resourcesTechnical literature
- SLN[X] datasheet ↗
Datasheet · PDF · 2 pages · View or save from the PDF viewer
- SLN[X] installation instructions ↗
Manual · PDF · 7 pages · View or save from the PDF viewer
- SLN[X] specification ↗
Specification · PDF · 1 pages · View or save from the PDF viewer
Manufacturer-hosted technical documents. Page links use PDF page numbers; some viewers open at the first page. Confirm the document revision and exact model before ordering.
SLN[X] is an exterior-mounted, single-lamp UV-C fixture with a NEMA 4 enclosure for indoor or outdoor HVAC equipment. It is used in projects involving cooling-coil surfaces, drain pans or airstream treatment. The treatment objective determines the lamp layout; choosing a fixture is one part of the system design.
Tillman & Associates helps South Texas contractors, engineers and facility teams identify existing fixtures and develop new or retrofit UV-C inquiries. You may see this product identified as Steril-Aire, UV Resources or UVR[X]. Include the actual equipment label when requesting parts.
Ask Tillman about an SLN[X] project →
How the fixture fits into an HVAC system
The enclosure mounts outside the duct, plenum or air-handling unit while the lamp projects into the treatment area. This arrangement provides exterior service access. The manufacturer lists rooftop units, supply/return/exhaust ducts and AHUs among the application starting points.
The datasheet describes a single-ended lamp, 120–277 V power supply and a lamp/power-supply monitoring signal. Published lamp lengths span 16 to 61 inches. Those details help begin a selection; lamp length alone does not establish adequate coverage or replacement compatibility.
Coil treatment and airstream treatment require different layouts
Coil and drain-pan treatment directs UV-C toward stationary surfaces. The layout must provide useful exposure across the target area rather than leave important sections shadowed.
Airstream treatment addresses microorganisms moving through the equipment. Exposure time is shorter and depends on airflow and the treatment zone. UV intensity, time and the target organism affect the required dose. A lamp arrangement intended to maintain a coil should not automatically be credited with a particular airborne reduction rate.
Tell us which objective matters to your project. If the specification requests a reduction percentage or a particular target organism, include that requirement and its stated design conditions. We will use it to guide the application review rather than infer performance from the fixture name.
SLN[X], SL[X] and DLN[X]: where to start
| Family | Basic arrangement | Selection question |
|---|---|---|
| SLN[X] | One projecting lamp; NEMA 4 enclosure. | Does the single-lamp arrangement fit the equipment and required coverage? |
| SL[X] | Indoor single-lamp fixture. | Is the enclosure suitable for the actual installation exposure? |
| DLN[X] | Two-lamp NEMA 4 fixture. | Does a dual-lamp layout better fit the treatment area? |
These are family distinctions, not statements of interchangeability. Review the exact fixture, lamps and mounting details before substituting equipment. Browse the UV-C fixture families and resources.
Installation planning: access, materials and lamp support
UV-C can injure eyes and skin. The installation instructions require access interlocks that remove lamp power, control of light leakage and protection of susceptible non-metallic components. Service personnel must disconnect power before access. Follow the complete fixture manual and the instructions supplied with accessory kits.
Check where the lamp will pass through the equipment wall, how it will be supported and how it can be removed for service. Include photographs or drawings of internal insulation, filters, wiring and the drain pan so the installer can review material exposure. A nominally long enough lamp is not useful if it cannot be installed or serviced correctly.
The manufacturer publishes separate lamp-support instructions. Send the fixture model, lamp identification and intended bracket arrangement to Tillman before requesting support hardware. Do not assume that a bracket used on another UV family will fit.
Operating limits: confirm the complete assembly
The current installation manual, revision E (November 2025), states a maximum lamp operating temperature of 150°F. The datasheet describes other temperature ranges for components and applications. We therefore confirm the fixture-and-lamp assembly against the project conditions instead of presenting a single broad temperature claim as universal.
Equipment operating capability also does not establish a treatment result at that condition. Airflow, temperature, humidity and the proposed lamp layout belong in the application review.
What to send for a UV-C selection or replacement
- The treatment goal: coil/drain-pan maintenance, airstream treatment or replacement parts.
- AHU/duct and coil-face dimensions, available lamp clearance and service access.
- Airflow, air temperature, humidity and any specified treatment-performance requirement.
- Indoor/outdoor exposure, supply voltage and desired monitoring or building-controls connection.
- Drawings or photos showing the proposed mounting position and nearby materials.
- For replacements: fixture label, existing lamp number, measured length and clear photos of the connector and both lamp ends.
Common SLN[X] questions
Does the enclosure rating tell me how well the air is disinfected?
No. Enclosure selection and UV treatment performance answer different questions. Treatment performance requires review of the actual airflow, exposure and layout.
Can a UV lamp stay in service as long as it still lights?
Visible light does not verify the required UV-C output. Follow the manufacturer’s replacement guidance for the installed lamp and record its service history.
Can I order a replacement by length alone?
No. Send the part number, connector photos and fixture label. Similar dimensions do not establish electrical or mechanical compatibility.
Technical references and Tillman assistance
- SLN[X] datasheet — Rev. A, construction and applications (PDF)
- SLN[X] / DLN[X] installation instructions — 57003530 E, November 2025 (PDF)
- Manufacturer white paper — airstream treatment and UV dose (PDF)
- Lamp identification and specifications (PDF)
- Monitoring and installation accessories
Technical content reviewed November 12, 2026. UL safety evaluation does not establish the product’s health effects or air-disinfection effectiveness, as noted in the manufacturer documents.
Need help with a fixture, lamp or proposed layout? Contact Tillman for selection, replacement and quotation assistance.
Related posts

Steril-Aire / UV Resources DEX (DE[X]) Double-Ended UV-C Fixture
Learn how DEX internal fixtures fit HVAC coil and airstream projects, what double-ended means, and how to identify replacement lamps and parts.
Technical literature
- DE[X] datasheet ↗
Datasheet · PDF · 2 pages · View or save from the PDF viewer
- DE[X] installation instructions ↗
Manual · PDF · 7 pages · View or save from the PDF viewer
- DE[X] specification ↗
Specification · PDF · 1 pages · View or save from the PDF viewer

Steril-Aire / UV Resources SLX (SL[X]) Indoor UV-C Fixture
Understand SLX indoor mounting, coil versus airstream applications, service clearance and replacement-lamp identification with Tillman.
Technical literature
- SL[X] datasheet ↗
Datasheet · PDF · 2 pages · View or save from the PDF viewer
- SL[X] installation instructions ↗
Manual · PDF · 6 pages · View or save from the PDF viewer
- SL[X] specification ↗
Specification · PDF · 1 pages · View or save from the PDF viewer